Medium Voltage Indoor Metering Cabinet integrates Class 0.2S metering, vacuum circuit breaking, and comprehensive protection in a single metal-clad draw-out Circuit breaker. It is located on the medium-voltage side for 11/12kV indoor substations and distribution rooms, using a high-side metering scheme to ensure metering accuracy and eliminate low-voltage tampering risks, and delivers reliable fault protection, and smart monitoring — all in a compact, maintenance-friendly footprint.
Ideal for 11/12kV substations, distribution rooms, industrial plants, data centers, and large commercial complexes.

Fully Enclosed MV/LV isolation Compartment Structure, Integrates metering, protection and monitoring

Provides multiple electrical protections including overload, short-circuit, and earth fault protection

Built-in temperature/humidity control and arc flash detection for real-time cabinet condition monitoring
| Model | KYN28-12 |
| Rated Voltage | 11 kV (highest system voltage: 12 kV / 17.5 kV) |
| Rated Current | 630 A (busbar and feeder breaker) |
| Short-Circuit Breaking Current | 31.5 kA (rms) |
| Short-Time Withstand Current | 31.5 kA / 3 s |
| Peak Withstand Current | 78 kA |
| Lightning Impulse Withstand Voltage | 95 kV pk 1.2/50μs |
| CT Accuracy Class | Class 0.2S (metering winding) |
| Meter Accuracy Class | Class 0.2S active / Class 1.0 reactive |
| Circuit breaker | Draw-out Vacuum Circuit Breaker |
| Applicable Standards | IEC 62271-100/200, IEC 61869, IEC 60255, IEC 60529, IEC 60298, IEEE 1613, ANSI C37 |